Captor effluent flows into two activated sludge basins for further treatment. The

average M.L.S.S. in the aeration basins during the summer months is 1400 to 1600

mg/l and during the winter months is 2200 mg/l. D.O. is maintained  at 2.5 to 3.5

mg/l by two direct drive centrifugal blowers with a third blower reserved for backup.

Air from the blowers is distributed throughout the basins by high efficiency EPDM

membrane diffusers. The sludge age ranges from 5 days to 15 days. The S.V.I. ranges

from 100 o 380 depending on the mode of operation.





Parameter

Inf. Avg. mg/l

 Range mg/l

Eff. Avg. mg/l

   Range mg/l

% Rem Avg.

CBOD

209

146-266

5

3.7-9

98

Sus. Sol.

211

145-290

4

2-11

98

Ammonia

17

6-23

2.6

.5-6

84